Count mode - process output data
The structure of the process output data depends on the module's parameterization.
1 Process output data with parameter values for:
Load value direct or
Load value in preparation or
Reference value 1 or
Reference value 2
2 Process output data with parameter values for:
Function and behavior of DO1/DO2
m = Offset of output data; depending on extension of station and the corresponding fieldbus.
Data Byte Byte DP/
PN
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output m m + 7
Load value direct
Load value in preparation,
Reference value 1
Reference value 2
(depending on the parameterization)
m + 1 m + 6
m + 2 m + 5
m + 3 m + 4
Con-
trol
m + 4 m + 3
EXTF_
ACK
CTRL_
DO2
SET_
DO2
CTRL_
DO1
SET_
DO1
RES_
STS
CTRL_
SYN
SW_
GATE
m + 5 m + 2
reserved
LOAD_
PRE-
PARE
LOAD_
VAL
LOAD_
DO_
PARAM
LOAD_
CMP_
VAL2
LOAD_
CMP_
VAL1
m + 6 m + 1
reserved
m + 7 m
Data Byte Byte DP/
PN
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output m m + 7 reserved MODE_DO2 reserved MODE_DO1
m + 1 m + 6 Hysteresis value
m + 2 m + 5 Pulse duration
m + 3 m + 4 reserved
Con-
trol
m + 4 m + 3 EXTF_
ACK
CTRL_
DO2
SET_
DO2
CTRL_
DO1
SET_
DO1
RES_
STS
CTRL_
SYN
SW_
GATE
m + 5 m + 2 LOAD
_
DO_
PARA
M
LOAD
_
CMP_
VAL2
LOAD
_
CMP_
VAL1
LOAD
_
PRE-
PARE
LOAD
_
VAL
m + 6 m + 1 reserved
m + 7 m
NOTE
Unlike the physical digital output DO1, output DO2 is only a data value that is indicated
with the data bit STS_DO2 of the process input.