Appendix A: Sensors A-10
Watlow EZ-Zone PM Express Temperature Controller D291511.18a.fm
10. In the Function of Output 1 Menu (Fn1) select Heat (hEAt). Press Advance twice to skip
the Output Type Menu and move on to the Function of Output 2 Menu.
11. In the Function of Output 2 Menu (Fn2) select Alarm (ALM). Press Advance.
12. In the Heat Algorithm Menu (h.Ag) select PID (Pid). Press Advance three times to skip
the Hysteresis & Cool Algorithm Menus and move on to the Alarm Type Menu.
13. In the Alarm Type Menu (A.ty) select Process Alarm (PrAL). Press Advance.
14. In the Alarm Hysteresis Menu (A.hy) select Units, 1.0° F or 1.0° C. Press Advance.
15. In the Alarm Logic Menu (A.Lg) select Close on Alarm (ALC). Press Advance.
16. In the Alarm Latching Menu (A.LA) select Non-Latching (nLAt). Press Advance.
17. In the Alarm Blocking Menu (A.bL) select Off (oFF). Press Advance.
18
. In the Alarm Silencing Menu (A.Si) select Off (oFF). Press Advance.
19. In the Alarm Display Menu (A.dSP) select On (on). Press Advance.
20. In the Ramp Action Menu (rP) select Off (oFF). Press Advance four times to skip the
Ramp Rate, Scale Low and Scale High Menus and move on to the Power Scale High
Output 1 Menu.
21. In the Power Scale High Output 1 Menu (o.hi1) select 100.0 . Press Advance.
22. In the Power Scale High Output 2 Menu (o.hi2) select 100.0 . Press Advance.
23. In the Upper or Left Display Menu (PAr1) select Active Process Value (AC.Pu). Press
Advance.
24. In the Lower or Right Display Menu (PAr2) select Active Set Point (AC.SP)Press
Advance.
25. In the Zone Address - Standard Bus Communication Menu (Ad.S) select 1. Press the
Infinity ke
y to escape from the Setup Menu and return to the Operations Menu.