EasyManua.ls Logo

Vertical Express ICON 32 - Page 146

Vertical Express ICON 32
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting I/O Issues Troubleshooting Section
©Vertical Express 4-14 Printed in USA April 2020
Troubleshooting I/O Issues
(continued)
1. Check the controller fault log for applicable faults.
2. If Ports 1 - 10 all display zeros, both the Safety Processor and the NTSD Processor
have mismatched I/O with the CPU.
a. Check the F1 pico fuse on the IOF Card.
b. Reload the controller generic files and the job configuration files. See Upload Soft-
ware to CPU Cards on page 6-36.
c. Configure the Safety Processor. See page 2-8.
d. From Startup Wizard, scroll to Clear HN Config? > Config HN/CN > Verify All CN's.
3. If the SP and NP I/O mismatch faults still exist, then communication is faulty between
the IOF and the CPUC. Replace the IOF or CPUC Cards.
Selector I/O Troubleshooting
Table 3 - Correct Selector I/O States
LVUR*, LVDR*,DZ1R*, DZ2R* are only used for close floors—for that close floor,
activate these I/Os instead of LVU, LVD, DZ1, DZ2.
The I/O states for Bits 5-8 are a copy of the first four bits shown in Port 15 at a close
landing; requires P12=1.
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
LVU LVD DZ1 DZ2 LVUR* LVDR* DZ1R* DZ2R*
@1 1 1 1 1 0 0 0 0
On Directional Limit Bottom 1 0 1 1 0 0 0 0
@top landing 1 1 1 1 0 0 0 0
On Directional Limit Top 0 1 1 1 0 0 0 0
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
TSR1 TSR2 NTST NTSB DL x x x
@1 0 0 0 1 0 x x x
On Directional Limit Bottom 0 0 0 1 1 x x x
@top landing 1 1 1 0 0 x x x
On Directional Limit Top 1 1 1 0 1 x x x
Port 16
Car PositionCar Position
Port 15

Table of Contents