Operational Adjustments Adjustment Section
©Vertical Express 2-40 Printed in USA April 2020
Additional Operational Adjustments
Verify the following settings:
1. TIM set correctly.
2. DAT set correctly.
3. L10 - L34 for lobby request (parking options) - some jobs ship with parking enabled.
4. Multistage jacks.
a. JRT set to desired time.
b. O29 = 6-10 seconds.
c. O44 - # motor starts to trigger a jack resync.
d. O30 - Jack resync interval in days (1-3).
e. O32 - Jack resync door.
5. Fire service.
a. F10 - Main fire return landing.
b. F11 - Alternate fire return landing.
6. Set Hoistway Access (optional).
• Z38 - Hoistway Access Bottom Floor Door Selection
• Z39 - Hoistway Access Top Floor Door Selection
• O11- Hoistway Access Bottom Zone
• O21- Hoistway Access Top Floor
• O22- Hoistway Access Top Zone
• Configure the Safety Processor
• Issue TECC Command