TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshoong
Ref.
No�
Display Descripon
Possible Causes Soluons
Condion Alert, Error or Fault
6 HYSECURITY
BAD POWER
Crically low 24V supply
power. This message can
occur only on inial start
up if power is crically
low.
DC power is below 14V –
no control funcons will be
allowed at all.
1. No AC Power. See item 3
above.
2. Wiring / Connector problem
– check all connecons.
Clean or repair as required.
3. Check baery condion.
Check power board power
switch for 115V or 230V and
match to incoming power.
7 No display. LED
blinking.
SmartDC Controller is
receiving power, but
baery voltage is very
low.
Several possible causes:
- The AC power has been
shut o from the operator
for too long and the
baeries are drained.
- Wiring problem.
- Baeries no longer hold a
charge.
- Bad SmartDC Controller.
- Bad transformer.
1. No AC power. See item 3
above.
2. Wiring / Connector problem
– check all connecons.
Clean or repair as needed.
3. Check baery condion.
4. SmartDC Controller charger
failure – check charger
voltage and replace
SmartDC Controller.
5. Transformer failure –
replace transformer.
8 HYSECURITY
LOADER
The SmartDC Controller
cannot locate the
system soware or
soware is being loaded
into the SmartDC
Controller.
There is no soware loaded
on the SmartDC Controller
or soware is currently
being loaded.
Load the latest soware
version (H5.XX) using S.T.A.R.T.
with a download cable
(preferably USB) or wait for
soware to nish loading.
9 ALERT 1
FORCE OPEN
Gate forced open. The gate has been forced
open from a full closed
limit and is being prevented
from re-closing. Must be
enabled in User Menu.
Will self-clear aer an open or
close input.