Table 5.25 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
0
6
200
1.3 2.5 50
12
Voltage (V)
Frequency (Hz)
0
6
200
1.5 3 60
12
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 6050
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 7260
Voltage (V)
Frequency (Hz)
Table 5.26 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
0
5
200
1.3 25 50
35
Voltage (V)
Frequency (Hz)
0
6
200
1.3 25 50
50
Voltage (V)
Frequency (Hz)
0
5
200
1.5 30 60
35
Voltage (V)
Frequency (Hz)
0
6
200
1.5 30 60
50
Voltage (V)
Frequency (Hz)
Table 5.27 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
7
200
1.3 2.5 50
15
Voltage (V)
Frequency (Hz)
0
9
200
1.3 2.5 50
20
Voltage (V)
Frequency (Hz)
0
7
200
1.5 3 60
15
Voltage (V)
Frequency (Hz)
0
11
200
1.5 3 60
20
Voltage (V)
Frequency (Hz)
Table 5.28 Constant Output, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
6
12
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
6.9
230
1.5 3 60
13.8
Voltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F. Refer to V/f Pattern on page 195 for an example custom V/f
pattern.
No. Parameter Name Setting Range Default
E1-04 Maximum Output Frequency 40.0 to 400.0 Hz 60.0 Hz
E1-05 Maximum Voltage
0.0 to 255.0 V
<4>
575.0 V
E1-06 Base Frequency 0.0 to [E1-04] 60.0 Hz
E1-07 Middle Output Frequency 0.0 to [E1-04] 3.0 Hz
E1-08 Middle Output Frequency Voltage
0.0 to 255.0 V
<4>
15.0 V
E1-09 Minimum Output Frequency 0.0 to [E1-04] 1.5 Hz
E1-10 Minimum Output Frequency Voltage
0.0 to 255.0 V
<4>
9.0 V
E1-11 Middle Output Frequency 2 0.0 to [E1-04]
0.0 Hz
<6>
E1-12 Middle Output Frequency Voltage 2
0.0 to 255.0 V
<4>
0.0 V
<5>
<6>
5.5 E: Motor Parameters
194
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20