EasyManua.ls Logo

YASKAWA P1000

YASKAWA P1000
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.10 Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor. Refer to Motor
Performance Fine-Tuning on page 290 for guidance on troubleshooting.
Motor hunting and oscillation
Poor motor torque
Poor speed precision
Poor motor torque and speed response
Motor noise
u
Common Problems
Common Problems Page
Cannot Change Parameter Settings 329
Motor Does Not Rotate Properly after Pressing RUN Button
or after Entering External Run Command
Motor Does Not Rotate 330
Motor Rotates in the Opposite Direction from the Run
Command
331
Motor Rotates in One Direction Only 331
Motor is Too Hot 331
oPE02 Error Occurs When Lowering the Motor Rated Current Setting 332
Motor Stalls During Acceleration or With Large Loads 332
Drive Frequency Reference Differs from the Controller Frequency Reference Command 333
Excessive Motor Oscillation and Erratic Rotation 333
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled 333
Noise From Drive or Motor Cables When the Drive is Powered On 334
Ground Fault Circuit Interrupter (GFCI) Trips During Run 334
Connected Machinery Vibrates When Motor Rotates
Unexpected Noise from Connected Machinery 334
Oscillation or Hunting 334
PID Output Fault 335
Insufficient Starting Torque 335
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking) 335
Output Frequency is not as High as Frequency Reference 335
Buzzing Sound from Motor at 2 kHz 335
Motor Does Not Restart after Power Loss 336
u
Cannot Change Parameter Settings
Cause Possible Solutions
The drive is running the motor
(i.e., the Run command is present).
Stop the drive and switch over to the Programming Mode.
Most parameters cannot be edited during run.
The Access Level is set to restrict access to parameter
settings.
Set the Access Level to allow parameters to be edited (A1-01 = 2).
The operator is not in the Parameter Setup Mode
(the screen will display “PAr”).
See what mode the operator is currently set for.
Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”
appears on the screen. Refer to The Drive, Programming, and Clock Adjustment Modes on
page 114.
A multi-function contact input terminal is set to allow
or restrict parameter editing
(H1-01 through H1-08 = 1B).
When the terminal is open, parameters cannot be edited.
Turn on the multi-function contact input set to 1B.
6.10 Troubleshooting without Fault Display
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
329
6
Troubleshooting

Table of Contents

Other manuals for YASKAWA P1000

Related product manuals