EasyManua.ls Logo

YASKAWA P1000

YASKAWA P1000
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name Description Values Page
o4-01
(50B)
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h. Default: 0
Min.: 0
Max.: 9999
272
o4-02
(50C)
Cumulative Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Default: 0
Range: 0, 1
273
o4-03
(50E)
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h. Default: 0
Min.: 0
Max.: 9999
273
o4-05
(51D)
Capacitor Maintenance
Setting
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
Default: 0%
Min.: 0
Max.: 150
273
o4-07
(523)
DC Bus Pre-Charge Relay
Maintenance Setting
Sets the value of the Maintenance Monitor for the soft charge bypass relay.
See U4-06 to check when the bypass relay may need to be replaced.
Default: 0%
Min.: 0
Max.: 150
273
o4-09
(525)
IGBT Maintenance Setting
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBT
replacement times.
Default: 0%
Min.: 0
Max.: 150
273
o4-11
(510)
U2, U3 Initialization
0: U2-oo and U3-oo monitor data is not reset when the drive is initialized
(A1-03).
1: U2-oo and U3-oo monitor data is reset when the drive is initialized
(A1-03).
Default: 0
Range: 0, 1
273
o4-12
(512)
kWh Monitor Initialization
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
Default: 0
Range: 0, 1
274
o4-13
(528)
Number of Run Commands
Counter Initialization
0: Number of Run commands counter is not reset when the drive is initialized
(A1-03).
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).
Default: 0
Range: 0, 1
274
o4-17
(3100)
Set/Reset Real-Time Clock
Sets the current date and time for the Real-Time Clock.
0: - -
1: Set
2: Reset
Default: 0
Range: 0 to 2
116
o4-20
(81F)
Time Display Format
Sets the time display format.
0: 12-hour
1: 24-hour
Default: 0
Range: 0, 1
274
B.11 o: Operator-Related Settings
472
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual

Table of Contents

Other manuals for YASKAWA P1000

Related product manuals