When this parameter is set to 0 (disabled) the drive will ignore the Run state of the drive when power is lost. When this
parameter is set to 1 (enabled), and the active Run source is from the digital operator, the drive will save the Run status during
power-down.
When power is restored, and the drive is still in operator mode, the previous Run status will be loaded and will apply the Run
command.
If the Run command was issued while the drive was running in LOCAL mode (triggered through the operator key) and power
was cycled, the drive will not automatically run, as the default starting state is REMOTE operation.
Note: The Run Status is saved on the terminal board and on the control card. If the Run Status does not match (e.g., if the terminal board was
replaced), the Run Status is reset and the drive will not run on the next power-up.
WARNING! Sudden Movement Hazard. If o2-20 is set to 1 and o2-06 is set to 0, the drive will continue running when the digital operator is
removed and may run automatically when power is cycled, resulting in death or serious injury. Clear all personnel from the drive, motor and
machine area before applying power. Secure covers, couplings, shaft keys and machine loads before applying power to the drive.
No. Name Setting Range Default
o2-20 Operator Run Save at Power Loss 0, 1 0
Setting 0: Disabled
Setting 1: Enabled
u
o3: Copy Function
These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting. Refer to Copy Function Related Displays on page 325 for a description of errors and displays.
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No. Name Setting Range Default
o3-01 Copy Function Selection 0 to 3 0
Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note: Set o3-02 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
n
o3-02: Copy Allowed Selection
Allows and restricts the use of the Copy function.
No. Name Setting Range Default
o3-02 Copy Allowed Selection 0, 1 0
Setting 0: Disabled
Setting 1: Enabled
u
o4: Maintenance Monitor Settings
n
o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No. Name Setting Range Default
o4-01 Cumulative Operation Time Setting 0 to 9999 0
5.10 o: Operator Related Settings
272
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20