b8: Energy Saving
No.
(Addr.
Hex)
Name Description Values Page
b8-01
(1CC)
Energy Saving Control
Selection
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
175
b8-04
(1CF)
Energy Saving Coefficient
Value
Determines the level of maximum motor efficiency. Setting range is 0.0 to
2000.0 for drives 3.7 kW and smaller. The display resolution depends on the
rated output power of the drive.
Default:
<1> <2>
Min.: 0.00
Max.: 655.00
175
b8-05
(1D0)
Power Detection Filter Time
Sets a time constant filter for output power detection. Default: 20 ms
Min.: 0
Max.: 2000
176
b8-06
(1D1)
Search Operation Voltage
Limit
Sets the limit for the voltage search operation as a percentage of the motor
rated voltage.
Default: 0%
Min.: 0
Max.: 100
176
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
B.3 b: Application