Three-Phase 600 V Class Drive Models 5A0125 to 5A0242
Table A.9 Power Ratings Continued (Three-Phase 600 V Class)
Item Specification
Drive Models 5A0125 5A0145 5A0192 5A0242
Maximum Applicable Motor Capacity (HP)
<1>
ND Rating 125 150 200 250
Input
Input Current (A)
<2>
ND Rating 129 158 228 263
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation -10 (-15) to +10%
Allowable Frequency Fluctuation ±5%
Input Power (kVA) ND Rating 147 181 261 301
Output
Rated Output Capacity (kVA)
<3>
ND Rating
<4>
124 144 191 241
Rated Output Current (A)
ND Rating
<4>
125 145 192 242
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 3 kHz
<4>
Maximum Output Voltage (V) Three-phase 500 to 600 V (proportional to input voltage)
Maximum Output Frequency (Hz) 400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings
402
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20

Related product manuals