Setting 2: Vendor Specific
Setting 3: Forward
Setting 4: Reverse
Note: Settings 2 to 4 are available in drive software versions PRG: 8503 and later.
n
F6-55: DeviceNet Baud Rate Monitor
Displays the baud rate currently being used for network communications. F6-55 is used only as a monitor.
No. Parameter Name Setting Range Default
F6-55 DeviceNet Baud Rate Monitor 0 to 2 (read only) 0
Setting 0: 125 kbps
Setting 1: 250 kbps
Setting 2: 500 kbps
n
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH - AC/DC Drive Object.
No. Parameter Name Setting Range Default
F6-56 DeviceNet Speed Scaling -15 to 15 0
F6-57 DeviceNet Current Scaling -15 to 15 0
F6-58 DeviceNet Torque Scaling -15 to 15 0
F6-59 DeviceNet Power Scaling -15 to 15 0
F6-60 DeviceNet Voltage Scaling -15 to 15 0
F6-61 DeviceNet Time Scaling -15 to 15 0
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
6
= 32000.
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No. Parameter Name Setting Range Default
F6-62 DeviceNet Heartbeat Interval 0 to 10 0
n
F6-63: DeviceNet Network MAC ID
Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No. Parameter Name Setting Range Default
F6-63 DeviceNet Network MAC ID 0 to 63 (read only) 63
n
F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)
5.6 F: Option Settings
204
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20

Related product manuals