Table B.7 400 V Class Drives Default Settings by Drive Model
No. Name Unit Default Settings
–
Model CIMR-Po
– 4A0002 4A0004 4A0005 4A0007
o2-04 Drive Model Selection Hex. 92 93 94 95
E2-11 Motor rated power kW (HP)
0.75
(0.75)
1.5
(2)
2.2
(3)
3.0
(3)
b3-04 V/f Gain during Speed Search % 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
– – – – –
b3-26 Start Speed Search Select – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 447.4 338.8 313.6 265.7
C5-17 Motor Inertia
kgm
2
0.0028 0.0068 0.0088 0.0158
C6-02 Carrier Frequency Selection – 7 7 7 7
E2-01 Motor Rated Current A 1.6 3.1 4.2 5.7
E2-02 Motor Rated Slip Hz 2.6 2.5 3 2.7
E2-03 Motor No-Load Current A 0.8 1.4 1.5 1.9
E2-05 Motor Line-to-Line Resistance Ω 22.459 10.1 6.495 4.360
E2-06 Motor Leakage Inductance % 14.3 18.3 18.7 19
E2-10 Motor Iron Loss for Torque Compensation W 26 53 77 105
L2-02 Momentary Power Loss Ride-Thru Time s 0.1 0.2 0.3 0.5
L2-03 Momentary Power Loss Min. Baseblock Time s 0.3 0.4 0.5 0.5
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.3 0.3 0.3
L3-24 Motor Acceleration Time for Inertia Calculations s 0.142 0.166 0.145 0.145
L8-02 Overheat Alarm Level °C 110 110 110 110
L8-35 Installation Method Selection – 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
B.16 Defaults by Drive Model
492
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual