H5-11: Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications. Refer
to Enter Command on page 536.
No. Name Setting Range Default
H5-11 Communications Enter Function Selection 0 or 1 0
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
n
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No. Name Setting Range Default
H5-12 Run Command Method Selection 0 or 1 0
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will
start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
C.4 MEMOBUS/Modbus Setup Parameters
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
513
C
MEMOBUS/Modbus
Communications

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20

Related product manuals