DP2 software version (DH)
È
Description of the display:
DP2 SFTWR.VER.
Software version of the Profibus DP interface
DP2 bus status (DI)
È
Description of the displays:
The displays are identical to the diagnostic displays of DP1 bus status (DE),
refer to page 102)
E1 value (DJ)
È
Description of the display:
E1 VALUE
Shows setpoint E1 in mA (only for standard I/O interface)
Internal faults 2 (DQ)
È
Description of the displays:
RAM FAILURE
RAM of the logic defective.
Remedy: Replace logic.
EEPROM FAILURE
EEprom of the logic defective. Remedy: Check logic, if necessary exchange
EEprom.
104
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP Manual
DP2 BUS STATUS DI
E1 VALUE DJ
INTERNAL FAULT 2 DQ
DP2 SFTWR.VER. DH