7-6
Chapter 7. PARAMETER SETUP
Example
Let’sregisterfourindividualitemsto
PARA
.Ifyoupress
PARA
inthe
basicdisplaystate,the1stto4thindividualitemsinthetablebelow
aredisplayedsuccessively.Inthisexample,letschangethesetting
values.
Order
Item to Call by
PARA
1 Setup data
C
0
1
2 PID parameter
P
-2
3 Variable parameter
F
L
4 Variable parameter
F
A
S
T
Thesettingsforregisteringtheseindividualitemsareasfollows:
SetupDataSetting“
SEt
No.
Item Code
[auxiliary
display]
Item
Setting
Value
Remarks
55
C
5
5
PARA
assignment
item 1
4501 This is produced by adding item No.1 of
C
0
1
to setup data radical 4500.
56
C
5
6
PARA
assignment
item 2
1511 This is produced by adding item No.11
of
P
-2
to PID parameter radical 1500.
57
C
5
7
PARA
assignment
item 3
2503 This is produced by adding item No.3
of
F
L
to setup data radical 2500.
58
C
5
8
PARA
assignment
item 4
2520 This is produced by adding item No.20
of
F
A
S
T
to variable parameter radical
2500.
Handling Precautions
• For details on item Nos., see 7-3 Parameter Setup List (pages 7-7
to 7-42).
• When the “
PARA
assignment item setting is set to a value that
does not correspond to an existing item, that setting is ignored.
For example, though factory setting 1000 corresponds to con-
stant-value operation data” 0th of base 1000, 0th does not exist,
so the setting will be treated an invalid data and will not be regis-
tered.