EasyManua.ls Logo

Azbil DCP31 - E d i (event 1 to 3 standby); D L i (event 1 to 3 ON delay time)

Azbil DCP31
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-23
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
2
E
D
1
Event 1 standby 0 0: Standby OFF
1: Standby ON
[Note]
The controller stands by after power
is restored and in the READY mode.
When the event type setting is ≥ 50,
“– – – –” is displayed and setting is not
possible.
3
H
Y
S
1
Event 1 hysteresis 5 0 to 200U (when event type is neither MV
nor MFB)
0.0 to 20.0 % (when event type is MV or
MFB)
[Note]
When the event type setting is ≥ 50,
“– – – –” is displayed and setting is not
possible.
4
D
L
1
Event 1 ON delay
time
0 0 to 3600s

Table of Contents