7-27
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory 
Setting
User 
Setting
Setting
10
E
 
D
 
3
Event 3 standby 0 0:  Standby OFF
1:  Standby ON
[Note]
   The controller stands by after power 
is restored and in the READY mode. 
When the event type setting is ≥ 50, 
“– – – –” is displayed and setting is not 
possible.
11
H
 
Y
 
S
 
3
Event 3 hysteresis 5 0 to 200U (when event type is neither MV 
nor MFB)
0.0 to 20.0% (when event type is MV or 
MFB)
[Note]
   When the event type setting is ≥ 50, 
“– – – –” is displayed and setting is not 
possible.
12
D
 
L
 
3
Event 3 ON delay 
time
0 0 to 3600s
13
T
 
T
Time event type 0 0:  T1 to T5 are all time events.
1:   T1 is a segment No. event. 
T2 to T5 are time events.
2:   T1 and T2 are segment No. events. 
T3 to T5 are time events.
3:   T1 to T3 are segment No. events. 
T4 and T5 are time events.
4:   T1 to T4 are segment No. events. 
T5 is a time event.
5:  All T1 to T5 are segment No. events.
[Note]
   On models not supporting time 
events, “– – – –” is displayed and set-
ting is not possible. 
Settings can be changed only in the 
READY mode.
14 - Unused
15 - Unused
16 - Unused