7-45
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
5
C
0
5
Input 1 range lower
limit (0%)
Not xed
-1999 to +9999U
[Note]
When the input 1 range type is non-
linear, “– – – –” is displayed and setting
is not possible.
When the input 1 range type is
changed from nonlinear to linear,
the original non-linear range values
remain.
The relationship between the analog
inputs and readout values can be
inverted by inverting the upper and
lower limit values.
6
C
0
6
Input 1 range upper
limit (100%)
Not xed
7
C
0
7
Input 1 root extrac-
tion dropout
0.0 0.0 to 10.0% (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 1 range type is non-
linear, “– – – –” is displayed and setting
is not possible.
8
C
0
8
Input 1 linearization
table approximation
0 0: Disabled
1: Enabled
[Note]
Table data setting (
a
,
b
) is used for the
linearization table.
9
C
0
9
SP1 lower limit 0%FS -1999 to upper limit U
[Note]
Changing the input 1 range has no
eect on the range.
However, note that a general reset sets
the range to the 0%FS value of the
input 1 range.
10
C
1
0
SP1 upper limit
100%FS
Lower limit to 9999U
[Note]
Changing the input 1 range has no
eect on the range.
However, note that a general reset sets
the range to the 0%FS value of the
input 1 range.