7-46
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory 
Setting
User 
Setting
Setting
11
C
 
1
 
1
PID set autoswitch-
ing (CH1)
0 0:  OFF (PID set segment designation)
1: ON
[Note]
   When set to 1, the PID set items in the 
program are invalid. 
The switching point for auto-switching 
is set in variable parameters (
C
 
P
 
.
 
1
 
1
 
to 
C
 
P
 
.
 
1
 
7
).
12
C
 
1
 
2
MV setting at input 1 
over-range (MV1)
0 0: OFF
1: ON
13
C
 
1
 
3
MV at input 1 over-
range
(MV1)
0 -10 to +110%
[Note]
   When 
C
 
1
 
2
 setting is 0, “– – – –” is 
displayed and setting is not possible.
14
C
 
1
 
4
Manual change 
mode (MV1)
0 0: Bump-less
1: Preset
[Note]
   When the programmer function is 
selected, operation is bump-less 
regardless of the setting of 
C
 
1
 
4
.
15
C
 
1
 
5
Preset manual value
(MV1)
0 -10 to +110%
[Note]
   When 
C
 
1
 
4
 setting is 0, “– – – –” is 
displayed and setting is not possible.
16
C
 
1
 
6
MV in READY mode 
(MV1, MV1 heat-cool 
output)
0 -10 to +110%
[Note]
   This setting is valid even if the pro-
grammer function is selected by 
C
 
1
 
8
 
setting. 
On heat/cool models, this setting func-
tions as the MV (heat) setting in the 
READY mode.
17
C
 
1
 
7
MV (cool) in READY 
mode (MV1 heatcool 
output)
0 -10 to +110%
[Note]
   When the model is not a heat/cool 
model, “– – – –” is displayed and set-
ting is not possible.
18
C
 
1
 
8
Main output type
(CH1)
0 0:  MV1 output (controller function)
1:  SP1 output (programmer function)
[Note]
   When the model is not a 5G output 
model, “– – – –” is displayed and set-
ting is not possible.