11-5
Chapter 11. SPECIFICATIONS
Item Specification
Control Auxiliary output Type PV, SP, deviation, MV, MFB
Scaling Supported
Output resolution 1/10000
Output 0D output 1
3D outputs 1, 2
Relay contact
output
Contact type: 1a1b
Contact rating: 5A (24Vdc, resistive load)
5A (120Vac, resistive load)
4A (240Vdc, resistive load)
Allowable contact voltage:
250Vac, resistive load
125Vdc, resistive load
Max. switching power: 150W, resistive load
960VA, resistive load
Life: 100,000 operations
(resistive load at contact
rating, frequency: 30
operations/minute)
Min. switching voltage: 5V
Min. switching current: 100mA
Output resolution: 1/1000
Time-proportional cycle: 5 to 120s
2G output 1 M/M drive relay Contact type: 1a (2 circuits)
Contact rating: 2.5A (30Vdc, L/R=0.7ms)
4A (120Vac, cosø=0.4)
2A (240Vac, cosø=0.4)
Allowable contact voltage:
250Vac, cosø=0.4
125Vdc, L/R=0.7ms
Max. switching power: 75W (L/R=0.7ms)
480VA (cosø=0.4)
Life: 100,000 operations
(cosø=0.4 at contact
rating, frequency: 30
operations/minute)
Min. switching voltage: 5V
Min. switching current: 100mA
MFB (motor feedback) input range:
100 to 2500Ω
Control at MFB (motor feedback) disconnection:
ON/OFF for continuation
of operation according to
MFB estimated position
can be selected.

Table of Contents