11-6
Chapter 11. SPECIFICATIONS
Item Specification
Output 5G output 1
5K outputs 1, 2
Auxiliary outputs 1, 2
Current output
(4 to 20mA)
Output current:
4 to 20mAdc/0 to 20mAdc
Allowable load resistance:
600Ω max. (under
operating conditions)
Output accuracy: ±0.1%FS max. (under
standard conditions)
±0.5%FS at output 5% or
less of 0 to 20mA output
Output resolution: 1/10000
Inrush current: 25mA max. for 50ms max.
(at 250Ω load)
Max. output current: 22.0mAdc
Min. output current: 0.0mAdc
Output updating cycle: 0.1s
Open terminal voltage: 25V max. (output 1)
18V max. (output 2,
auxiliary outputs 1, 2)
6D output 1
5K outputs 1, 2
(when current output
is switched to voltage
output)
Voltage output Allowable load resistance:
600Ω max. (under
operating conditions)
Inrush current: 25mA max. for 50msmax.
(at 250Ω load)
Load current adjustment: 2 to 22mA variable
Open terminal voltage: 25V max.
18V max. (output 2 of 5K
output)
OFF leakage current: 100μA max.
Output response time: At ON-OFF 600Ω load:
0.5ms max.
At OFF-ON 600Ω load:
1.0ms max.
Output resolution: 1/1000
Time-proportional cycle: 1 to 60s variable
Event/
Time
event
Output
Events 1, 2 Relay contact
output
Contact type: 1a
Contact rating: 1A (240Vac/30Vdc,
resistive load)
Life: 100,000 operations (at
rating)
Min. switching voltage, current:
10V, 10mA
Event 3 Relay contact
output
Contact type: 1a1b
Contact rating: 2A (240Vac/30Vdc,
resistive load)
Life: 100,000 operations (at
rating)
Min. switching voltage, current:
10V, 10mA

Table of Contents