EasyManua.ls Logo

B&R Automation PC 620 - Four Automation Panel 900 Units Via SDL (Onboard); Basic System Requirements

B&R Automation PC 620
594 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
230
Commissioning • Connection examples
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
4.6 Four Automation Panel 900 units via SDL (onboard)
An Automation Panel 900 is connected to the integrated SDL interface (onboard) via an SDL
cable. Up to three other Automation Panels of the same type are connected to this Automation
Panel and operated via SDL. All four panels show the same content (Display Clone).
USB is supported up to a maximum distance (SDL segment 1 + SDL segment 2) of 30 m on the
first two panels (front and back side). From a distance of 30 m and longer, USB is only available
for the first panel (front and back side). USB devices can only be connected directly to the
Automation Panel (without a hub).
4.6.1 Basic system requirements
The following table shows the possible combinations for the APC620 system unit with CPU
board to implement the configuration shown in the figure above. If the maximum resolution is
limited when making the combination then it is also shown in this table (e.g. for connecting a non-
B&R Automation Panel 900 device).
Figure 99: Configuration - Four Automation Panel 900 units via SDL (onboard)
CPU board with system unit
Restriction
Resolution
5PC600.SX01
-00
5PC600.SX02
-00
5PC600.SX02
-01
5PC600.SF03
-00
5PC600.SX05
-00
5PC600.SX05
-01
5PC600.SE00
-00 / -02
5PC600.X945-00 - --✓✓Max. UXGA
Table 135: Possible combinations of system unit and CPU board
Automation PC 620
with AP Link
5AC600.SDL0-00
SDL segment 1
max. 40 m
Link: 5DLSDL.1000-01
USB
not possible
Link: 5DLSDL.1000-01
USB OK
0
2
Graphics Engine 1
x
Internal APC620 panel number
Link: 5DLSDL.1000-01
1
Link: 5DLSDL.1000-00
3
SDL segment 2
max. 40 m
SDL segment 3
max. 40 m
SDL segment
max. 40 m
USB
not possible
USB
possible
Monitor / Panel
connection
independent of segment length depends on segment length

Table of Contents