Required environmental conditions
Manual b maXX
®
BM1000
Document No. 5.07003.04 Baumüller Nürnberg GmbH
142
of 174
D.1
D.1 Required environmental conditions
D.2 Non-electrical data
1)
98/37/EG, appendix I, chapter 1.7.4.f, paragraph 8
Operation Air Temperature: -10 to +50 °C (14 to 122 °F)
-10 to +40 °C (14 to 104 °F)
for side-by-side mounting
Relative Humidity: < 90 %, no condensation allowed
Atmospheric pressure: 86 to 106 kPa
Installation Site Altitude: < 1000 m
Vibration: < 20 Hz: 9.80 m/s
2
(1G) max
20 to 50 Hz: 5.88 m/s
2
(0.6 G) max
Storage
Transportation
Temperature: -20 °C to +60 °C (-4 °F to 140 °F)
Relative Humidity: < 90 %, no condensation allowed
Atmosphere pressure: 86 to 106 kPa
Vibration: <20 Hz: 9.80 m/s
2
(1 G) max
20 to 50 Hz: 5.88 m/s
2
(0.6 G) max
Pollution Degree 2 suitable for a factory type environ-
ment.
NOTE
m Operating, storing or transporting the b maXX
®
BM1000 outside these conditions may
cause damage to the device.
m Failure to observe these precautions may void the warranty!
Device
b maXX
®
BM1000
Dimensions
(W x H x D)
Weight with controller,
without plug-in modules
Noise
emission
Frame 1 72 x 142 x 152 mm 1.2 kg max. 54 db(A)
1)
Frame 2 100 x 174 x 152 mm 1.9 kg max. 54 db(A)
1)
Frame 3 130 x 260 x 170 mm 4.2 kg max. 63 db(A)
1)