EasyManua.ls Logo

Baumuller b maXX BM1000 - Analog Current Input; Analog Output Meter

Baumuller b maXX BM1000
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Terminals
Manual b maXX
®
BM1000
Document No. 5.07003.04 Baumüller Nürnberg GmbH
64
of 174
6.11
Keep control wiring as far away as possible from the power wiring and in separate con-
duits to avoid interference. If necessary let them cross only at 90º angle.
The device control wiring should be properly installed and not touch any live power wir-
ing or terminals.
ACI Analog current input
Figure 35: Analog current input
Impedance: 250 Ω
Resolution: 10 bits
Range: 4 to 20 mA =
0 to max. output frequency (P0033)
Selection: P0801, P0809, P1359
Set-up: P1128 to P1132
AFM Analog output meter
Figure 36: Analog output meter
0 to 10 V, 2 mA
Impedance: 20 kΩ
Output current 2 mA max.
Resolution: 8 bits
Range: 0 to 10 V
DC
Function: P1162 and P1163
ACM Analog control signal (ground) Ground for AVI, ACI, AFM
Terminal
symbol
Terminal function Factory settings (NPN mode)
ON: connect to DCM
NOTE
If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to the device. EMI can also be reduced by lowering the carrier frequency.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensi-
tivity of 200 mA, and not less than 0.1-second detection time to avoid noise tripping.

Table of Contents

Related product manuals