Applications for mains chokes
Manual b maXX
®
BM1000
Document No. 5.07003.04 Baumüller Nürnberg GmbH
70
of 174
6.15
Correct wiring
Figure 41: Application 2 mains choke
Correct wiring
Figure 42: Application 3 mains choke
Application 2 Question
Silicon rectifier and device are connected
to the same power.
Switching spikes will be generated when
the silicon rectifier switches on/off. These
spikes may damage the mains circuit.
Application 3 Question
Used to improve the input power factor, to
reduce harmonics and provide protection
from AC line disturbances (surges, switch
-
ing spikes, short interruptions, etc.). The
chokes should be installed when the
power supply capacity is 500 kVA or more
and exceeds 6 times the inverter capacity,
or the mains wiring distance 10
m.
When the mains power capacity is too
large, line impedance will be small and the
charge current will be too high. This may
damage b
maXX
®
BM1000 drive due to
higher rectifier temperature.