57
AS Interface - Design
NOTE!
If all 3 solenoid valves are simultaneously controlled via the AS interface, the electronics will activate the
valvessequentiallywitha200mstimedelaytoprotectthebusfromoverloads.
External power supply for solenoid valves:
External power supply: 19.2 V DC to 31.6 V DC
The power supply unit must include a secure disconnect in
accordance with IEC 60364-4-41. It must conform to the SELV
standard. The ground potential must not have a ground connection.
Power consumption from external
power supply for outputs
(solenoidvalves)-withoutintegrated
currentlimiting: <110mAat24VDC(for200msafterswitchingonofthe3.
rd
valve)
Power consumption from AS-i
forinputsanddisplay: <150mA(incl.externalinitiator,feedbackandfaultdisplay)
Integrated short-circuit protection
Pleaseconsiderthefollowinginformationtopowerrequirementandtothemaximumexpansion
stage of the AS interface network in chapter “12.3Numberofconnectablecontrolheads” and in the
ASinterfacespecications,whereapplicable.
12.6 Design aid
Design aid for supply of the valves via the AS-i bus
Power consumption of the electronics:
P
El
=1.0W or I
El
=33mA at 30.5 V
Power consumption of a valve during activation (200 ms):
P
Valve-ON
=0.9W or
I
Valve-ON
=30mA at 30.5 V
Power consumption of a valve after reduction:
P
Valve
=0.6W or I
Valve
=20mA at 30.5 V
Power consumption of an optical position report:
P
LED
=1.0W or I
LED
=33mA at 30.5 V
For the design of the maximum line lengths observe chapter
“12.4Maximumlengthofthebusline”.
Even if several control head valves are switched simultaneously via the bus, the switching signal is
passed on to the valves in staggered order, i.e. only one valve is ever taken up 0.9 W.
english
Control Head Type 8681