EasyManua.ls Logo

Burkert 8681 - Control Head Network Configuration

Burkert 8681
166 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
110
büS/CAN open-Design
15.18 Conguration of the control head network
ThegatewayTypeME43isusedasaeldbusinterfacebetweenthecontrolheads(Type8681büS/CANopen)
andthemastercontroller(EtherNet/IP).Eachgatewaycancommunicatewithupto63controlheadsofType
8681 büS/CANopen.
To set up a network, it is necessary to assign a unique device address to each control head(to
do so, use the respective DIP switches - see chapter “15.14.2”onpage97).
If there are less than 63 control heads connectedtoagateway,itisnecessaryto“hide”thenon-
existing control heads, namely both the inputs and the outputs.
Thereare2optionsto“hide”theinputsandoutputs:
viasoftware“LogixDesigner”(“15.18.1”)orviathe“BürkertCommunicator”Type8920(“15.18.2”).
15.18.1 “Hide function” via software “Logix Designer”
Startthe“LogixDesigner”
Opentheproject(e.g.“LogixDesigner-Gateway_Type8681”)
Openthedesiredgatewayandselectthe“Parameters”tab
Nowselecttheline“HideOutputs1-64”and“hide”eachnon-existentcontrolheadbysettinga“1”(one)
ineacheldfortheoutputs.
Nowselecttheline“HideInputs1-64”and“hide”eachnon-existentcontrolheadbysettinga“1”(one)
ineacheldfortheinputs.
Clickonthe“Set”buttontosaveitandtotransferittothegateway
After doing these steps, restart the whole system:itisrecommendedtoswitchoandswitchonthe
correspondingpowersupplyunit!Thenetworkcongurationhasthenbeencompleted.
english
Control Head Type 8681

Table of Contents

Other manuals for Burkert 8681

Related product manuals