IO-Link - Design
Inputs (control head –> IO-Link master/PLC) / binary or analogue feedback signals:
The recovery of the valve positions 3 reported back in binary format or the analogue position signal is
described in chapter “20PositionMeasuringSystem”onpage129. The analogue target position signal
(resolution:0.1mm)isavailableasacyclicvalue/parameter.
Outputs(IO-Link master/PLC –> Control head)/solenoidvalves:
Typ.switchingcapacity: 0.9W(persolenoidvalve,for200msafterthepowerhasbeenswitchedon)
Typ. continuous capacity:
0.6W(persolenoidvalvefrom200msafterthepowerhasbeenswitchedon)
Reduction in output: Integrated via the IO-Link electronics
Typ.inrushcurrent: 38mAor0.9W/200ms(persolenoidvalve)
Typ.holdcurrent: 25mAor0.6Wat24VDC(persolenoidvalve)
Operationmode: Continuousoperation(100%dutycycle)
Valve types: 6524
Central display of the switching statuses:
Current consumption from IO-Link
at24VDC: Approx21mAforapowersupplyof24VDCforeachindicatorlightshown;
for colour switching see chapter “21LEDColourAssignments”onpage
136
english
Control Head Type 8681