Engineer Menu 1-4 Engineering Manual
52
06 – P.A. Alarm
Activates when a PA Silent or PA Audible zone (page 27) triggers, or if a user code of type
Panic Code is used. The output activates only if the zone or user code belongs to the
selected ward. The output also activates if a user code of type Duress Code is used while
the ward is being unset. The output deactivates when all such alarms applicable to the
ward have been reset.
07 – Fire Alm.
Activates when any Fire zone (see page 27) that is in the selected ward triggers. The
Unset Fire attribute (page 38) determines whether the output activates only when the
zone is set, or when the zone is either set or unset. The output deactivates when all Fire
alarms in zones associated with the ward have been reset.
08 – Set
Activates when the selected ward is set; deactivates when the selected ward is unset.
09 – 2nd Entry
Activates when the selected ward's 2nd Entry Dly timer is running (page 59).
10 – 24Hr Alm.
Activates when a 24 Hour zone (page 26) in the selected ward goes into the alarm state
if the panel is unset; deactivates when the alarm is reset.
11 – Cnf Alarm
Activates when a confirmed alarm (page 77) is detected by a zone in the selected
ward, and remains active until reset.
12 – Zone Omit
Activates when any zone in the selected ward is omitted or shunted (e.g. by user option
1-2 or 1-3); deactivates when all zones in the selected ward have the omits/shunts
removed.
13 – Act. Omit
If a latching sensor (such as a door contact or break glass, but NOT a PIR) activates a
zone in the selected ward, and the zone remains active until the end of the confirmation
time (page 58), the control panel omits the active zone and triggers the Active Omit
output. The control panel deactivates the output when a user resets the system.
14 – 24Hr Omit
Activates when the selected ward has one or more 24 Hour zones omitted; deactivates
when the selected ward has all its 24 Hour zones reinstated.
15 – Set Fail
Activates when the selected ward fails to set (e.g. because a zone is active); deactivates
when the selected ward is reset.
16 – Settling
Activates when the Exit Settle timer (page 59) is running for the selected ward.
17 – Clear
Activates when the selected ward has no tamper conditions and no zones activated.
The output deactivates when the selected ward has a tamper or zone activation.