EasyManuals Logo

Danfoss FC 300 Design Guide

Danfoss FC 300
309 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #167 background imageLoading...
Page #167 background image
FC 300 Design Guide
How to Program
1-66 Min. Current at Low Speed
Range:
0-VariableLimit%
*
100%
Function:
Enter the minimum motor current at low speed, see
par. 1-53 Model Shift Frequency. Increasing this
current impr oves motor torque at low speed.
Par. 1-6 6 is enabled when par. 1-00 Configuration
Mode = Speed open-loop [0] only. The drive
runs with constant current through m otor
for speeds below 10 Hz.
For speeds above 10 Hz, the motor flux model in
the drive controls the motor. Par. 4-16 To rque
Limit Motor Mode and / or par. 4-17 Torque
Limit Generator Mode automatically ad just par.
1-66. The parameter with the highest value
adjusts par. 1-66. The current setting in par.
1-66 is composed o f the torque generating
current and the magnetizing current.
Example: Set par. 4-16 Torque Lim it for Motor
Mode to 100% and set par. 4-17 Torque Limit for
Generating Mode to 60%. Par. 1 -66 automatically
adjusts to about 127%, depending on the motor size.
This parameter is available for the FC 302 only.
1-67 Load Type
Option:
*
Passive load [0]
Active load [1]
Function:
Select passive load [0] for conveyers, fan and pum p
applications. Select active load [1] for hoisting
applications. When active load [1] is selected, set
par. 1-66 Min. Current at low speed to a level
which c orresponds with maximum torque.
This parameter is available for the FC 302 only.
1-68 Minimum Inertia
Range:
0-VariableLimit
*
Depending on motor data
Function:
Enter the minimum moment of inertia of the
mechanical system. Par. 1-68 and par. 1-69
Maximum Inertia are used for pre-adjustment of
the proportiona l gain in the speed control, see
par. 7-02 Speed PID P roportional Gain.
This parameter is available for the FC 302 only.
1-69 Maximum Ine rtia
Range:
0-VariableLimit
*
Depending on motor data
Function:
Enter the maximum moment of inertia of the
mechanical s ys tem. Par. 1-68 Minimum I nertia
and par. 1-69 are used for pre-adjustment of
the proportional gain in the speed control, see
par. 7-02 Speed PID Proportional Gain.
This parameter is available for the FC 302 only.
" 1-7* Start Adjustments
Parameters for setting special motor start features.
1-71 Start Delay
Range:
0.0 - 10.0 s
*
0.0s
Function:
This parameter refers to the start function
selected in par. 1-72 Start Function.
Enter the time delay required be fore
commencing acceleration.
1-72 Start Function
Option:
DC hold/d elay time [0]
DC Brake/delay time [1]
*
Coast/delay time [2]
Start speed/ current clockwise operation [3]
Horizontal operation [4]
VVC
plus
/Flux clockwise [5]
Function:
Select the start function duri ng start delay. This
parameter is linked to par. 1-71 Start Delay.
Select DC hold/delay time [0] to energize the
motor w ith a DC holding current (par. 2-00)
during the sta rt delay time.
Select DC brake/delay time [1] to energize the
motor with a DC braking current (par. 2-01)
during the sta rt delay time.
Select Coast/delay t ime [2 ] to releas e the
shaft coasted drive during the start delay
time (inverter off).
[3] and [4] are only possible with VVC+.
Select Start speed/current clockwise [3 ] to
connect the function described in par. 1-
74
*
default setting ()display text []value for use in communication via serial communication port
167
MG.33.B
6.22 - V LT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Output Voltage0-100% of supply voltage

Related product manuals