FC 300 Design Guide
How to Install
" Safe Stop Installation (FC 302 only)
To ca rry out an installation of a category 0 stop
(EN60204) in conformance with safety category
3 (EN954-1), follow these instructions:
1. The bridge (jumper) between terminal 37 and
24 V DC of the FC 302 must be removed.
Cutting or breaking the jumper is not sufficient.
Remove it entirely to avoid shor t-circuiting.
See jumper on illustration.
2. Connect terminal 37 to 24 V DC by a
short circuit-protected cable. The 24 V DC
voltage supply must be interruptible by an
EN954-1 category 3 circuit inte rrupt device.
If the interrupt device and the adjustable
frequency drive are placed in the same
installation panel, you can use a regular
cable instead of a protected one.
Bridge jumper between term inal 37 and 24 VDC.
The illustration below shows a s topping cate gory 0 (EN 60204-1) with safety cat. 3 (EN
954-1). The circuit interrupt is caused by an opening door contact. The illustration also
shows how to connect a non-safety-rela
ted hardware coast.
Illustration of t he essential aspects of an inst allat ion to achieve a stopping category 0 (EN
60204-1) with safety cat. 3 (EN 954-1).
112
MG.33.B6.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Output Voltage0-100% of supply voltage

Related product manuals