The F C 300 AutomationD rive DC link capacitors remain charged after power has been
disconnected. To avoid an electrical shock hazard, disco nn ect t he FC 300 from the p ower
supply before carrying out
maintenance. Wait at least as long as follows before servicing the
adjustable frequency drive:
FC 300: 0.34 – 10 HP
[0.25–7.5
kW]
4minutes
FC 300: 14.75 – 29.5
HP [11 – 22
kW]
15 minutes
BeawarethattheremaybehighvoltageontheDClinkevenwhentheLEDsareturnedoff.
13