FC 300 Design Guide
How to Program
" Initialization to Default Settings
Initialize the adjustable frequency drive to default settings in two ways:
R
ecommended initialization (via par. 14- 22)
1. Select par. 14-22
2. Press [OK]
3. Select "Initialisation"
4. Press [OK]
5. Cut off the mains supply and wait until
the display turns off.
6. Reconnect the mains supp ly - the adjustable
frequency drive is now reset.
Par. 14-22 initializes everything except:
14-50 RFI 1
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-char Delay
15-00 to 15-05 Operating data
15-20 to 15-22 Historic log
15-30 to 15-32 Fault log
Manual initialization
1. Disconnect from mains and wait until
the display turns off.
2. Press [Status] - [Main Menu] - [OK]
at the same time:
3. Reconnect mains supply while pre ssing the keys.
4. Release the keys after 5 s.
5. The adjustable frequency drive is now
programmed according to default settings.
This parameter initializes everything except:
15-00 Operating H ours
15-03 Power-ups
15-04 Over temps
15-05 Over volts
NOTE
When you carry out manual initializ
ation,
you also reset serial communication,
RFI filter settings (par. 14 -50)
and fault log settings.