72 = AHF Cap Disconnect
73 = AHF Cap Disconnect Inv
74 = Run indication
75 = Motor Switch Open
See P3.5.3.2.1. Not visible if only 2 output relays are installed.
See P3.5.3.2.2. Not visible if only 2 output relays are installed.
See P3.5.3.2.3. Not visible if only 2 output relays are installed.
The Digital Outputs of the Expander Slots C, D, and E
N O T I C E
Shows only the parameters for the outputs on option boards in slots C, D, and E. Make the selections as in Basic AO1 Function
(P3.5.4.1.1). This group or these parameters are not visible if there are no digital outputs in slots C, D, or E.
Table 52: Analog Output Settings on Standard I/O board
0 = TEST 0% (Not used)
1 = TEST 100%
2 = Output freq (0 - fmax)
3 = Freq reference (0 - fmax)
4 = Motor speed (0 - Motor nominal speed)
5 = Output current (0 - InMotor)
6 = Motor torque (0 - TnMotor)
7 = Motor power (0 - PnMotor)
8 = Motor voltage (0 - UnMotor)
9 = DC link voltage (0–1000 V)
10 = PID Setpoint (0–100%)
11 = PID Feedback (0–100%)
12 = PID1 output (0–100%)
13 = Ext.PID output (0–100%)
AB298035655957en-000201 / DPD01083 | 101Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide