11 Parameter Descriptions
11.1 (ID 212) Application
Location in the menu: P1.2
Use this parameter to select the application configuration for the drive. The applications include preset application configurations,
that is, sets of predefined parameters. The selection of the application makes the commissioning of the drive easy and reduces the
manual work with the parameters.
W A R N I N G
ACCIDENTAL START BECAUSE OF CHANGE OF SETTINGS
Running the Startup wizard, changing the application or the software can cause the I/O functions to change.
Disconnect the motor from the drive if an accidental start can be dangerous.
When the value of this parameter changes, a parameter groups get their preset values. The value of this parameter can be changed
when the starting up or commissioning the drive.
If this parameter is changed in the control panel, an application wizard starts and helps to set the basic parameters related to the
application. The wizard does not start, when using the PC tool to change this parameter. For more data about the application wiz-
ards, see 4.1 Application Wizards.
These applications are available:
0 = Standard
1 = HVAC
3 = PID control
4 = Multi-ump (single drive)
5 = Multi-ump (multidrive)
N O T I C E
When the application is changed, the contents of the Quick Setup menu change.
11.2 Trend Curve
11.2.1 (ID 2368) Sampling Interval
Location in the menu: P2.2.2
Use this parameter to set the sampling interval.
11.2.2 (ID 2369) Channel 1 MIN
Location in the menu: P2.2.3
This parameter is used in scaling by default. Adjustments can be necessary.
11.2.3 (ID 2370) Channel 1 MAX
Location in the menu: P2.2.4
This parameter is used in scaling by default. Adjustments can be necessary.
11.2.4 (ID 2371) Channel 2 MIN
Location in the menu: P2.2.5
This parameter is used in scaling by default. Adjustments can be necessary.
11.2.5 (ID 2372) Channel 2 MAX
Location in the menu: P2.2.6
This parameter is used in scaling by default. Adjustments can be necessary.
AB298035655957en-000201 / DPD01083166 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON 100 FLOW Series and is the answer not in the manual?

Danfoss VACON 100 FLOW Series Specifications

General IconGeneral
BrandDanfoss
ModelVACON 100 FLOW Series
CategoryDC Drives
LanguageEnglish

Related product manuals