11.4.10 (ID 524) Start Delay
Location in the menu: P3.2.9
Use this parameter to set the delay between the start command and the actual start of the drive.
11.4.11 (ID 181) Remote to Local Function
Location in the menu: P3.2.10
Use this parameter to set the selection of copy settings when going from Remote to Local (keypad) control.
11.4.12 (ID 15555) Restart Delay
Location in the menu: P3.2.11
Use this parameter to set the time delay during which the drive cannot be restarted after the drive has been stopped. The parame-
ter is used in compressor applications.
11.5 References
11.5.1 Frequency Reference
It is possible to program the source of the frequency reference in all the control places, except the PC tool. When using PC, it always
takes the frequency reference from the PC tool.
Remote Control Place (I/O A)
To set the source of the frequency reference for I/O A, use the parameter P3.3.1.5.
Remote Control Place (I/O B)
To set the source of the frequency reference for I/O B, use the parameter P3.3.1.6.
Local Control Place (Keypad)
If the default value keypad for the parameter P3.3.1.7 is used, the reference that was set for P3.3.1.8 Keypad Reference applies.
Remote Control Place (Fieldbus)
If the default value fieldbus for the parameter P3.3.1.10 is used, the frequency reference comes from fieldbus.
11.5.1.1 (ID 101) Minimum Frequency Reference
Location in the menu: P3.3.1.1
Use this parameter to set the minimum frequency reference.
11.5.1.2 (ID 102) Maximum Frequency Reference
Location in the menu: P3.3.1.2
Use this parameter to set the maximum frequency reference.
11.5.1.3 (ID 1285) Positive Frequency Reference Limit
Location in the menu: P3.3.1.3
Use this parameter to set the final frequency reference limit for the positive direction.
11.5.1.4 (ID 1286) Negative Frequency Reference Limit
Location in the menu: P3.3.1.4
Use this parameter to set the final frequency reference limit for the negative direction. Use this parameter for example to prevent
the motor from running in the reverse direction.