Danfoss VACON 100 FLOW Series - Group 3.16: Maintenance Counters

Danfoss VACON 100 FLOW Series
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = Enabled
P3.15.18.2
Supervision Alarm Level
P3.13.1.5
P3.13.1.6
P3.13.1.4
0.00
1699
Table 93: Pump Running Time Counter Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.15.19.1
Set Run-time Counter
0
1
0
1673
0 = No action
1 = Set the value that is specified by P3.15.19.2
to the run-time counter of the selected pump.
P3.15.19.2
Set Run-time Counter:
Value
0
300 000
h
0
1087
P3.15.19.3
Set Run-time Counter:
Pump Selection
0
8
1
1088
0 = All Pumps
1 = Pump (1)
2 = Pump 2
3 = Pump 3
4 = Pump 4
5 = Pump 5
6 = Pump 6
7 = Pump 7
8 = Pump 8
P3.15.19.4
Pump RuntimeAlarm
Limit
0
300 000
h
0
1109
0 = Not Used
P3.15.19.5
Pump Run-time FaultLi-
mit
0
300 000
h
0
1110
0 = Not Used
Table 94: Advanced Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.15.22.1
Staging Frequency
P3.3.1.1
320.0
Hz
320.0
15545
P3.15.22.2
De-staging Frequency
0.0
P3.3.1.2
Hz
0.00
15546
P3.15.22.3
Staging Delay
0
3600
s
15588
0
0 = bandwidth delay used
P3.15.22.4
De-staging Delay
0
3600
s
15589
0
0 = bandwidth delay used
6.16 Group 3.16: Maintenance Counters
Table 95: Maintenance Counters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.16.1
Counter 1 Mode
0
2
0
1104
0 = Not used
1 = Hours
2 = Revolutions * 1000
P3.16.2
Counter 1 Alarm Limit
0
2147483647
h/kRev
0
1105
0 = Not used
AB298035655957en-000201 / DPD01083 | 125Danfoss A/S © 2023.08