Use this parameter to select the digital input signal that prevents to start the drive. The drive can be ready but start is not possible
when the state of the interlock signal is 'open' (damper interlock).
11.7.4.17 (ID 1042) Run Interlock 2
Location in the menu: P3.5.1.17
Use this parameter to select the digital input signal that prevents starting the drive. The drive can be ready but start is not possible
when the state of the interlock signal is 'open' (damper interlock).
If an interlock is active, the drive cannot start.
It is possible to use this function to prevent the start of the drive when the damper is closed. If an interlock is activated during the
operation of the drive, the drive stops.
11.7.4.18 (ID 1044) Motor Preheat ON
Location in the menu: P3.5.1.18
Use this parameter to select the digital input signal that activates Motor Preheat function. The Motor Preheat function feeds DC-
current to the motor when the drive is in the stop state.
11.7.4.19 (ID 408) Ramp 2 Selection
Location in the menu: P3.5.1.19
Use this parameter to select the digital input signal that selects the ramp time to be used.
11.7.4.20 (ID 415) Acc/Dec Prohibit
Location in the menu: P3.5.1.20
Use this parameter to select the digital input signal that prevents the acceleration and the deceleration of the drive. No acceleration
or deceleration is possible until the contact is open.
11.7.4.21 (ID 419) Preset Frequency Selection 0
Location in the menu: P3.5.1.21
Use this parameter to set the digital input signal that selects the preset frequencies.
11.7.4.22 (ID 420) Preset Frequency Selection 1
Location in the menu: P3.5.1.22
Use this parameter to set the digital input signal that selects the preset frequencies.
11.7.4.23 (ID 421) Preset Frequency Selection 2
Location in the menu: P3.5.1.23
Use this parameter to set the digital input signal that selects the preset frequencies.
11.7.4.24 (ID 418) Motor Potentiometer Up
Location in the menu: P3.5.1.24
Use this parameter to increase the output frequency with a digital input signal. The motor potentiometer reference INCREASES until
the contact is open.
11.7.4.25 (ID 417) Motor Potentiometer Down
Location in the menu: P3.5.1.25
Use this parameter to decrease the output frequency with a digital input signal. The motor potentiometer reference DECREASES
until the contact is open.
11.7.4.26 (ID 1213) Quick Stop Activation
Location in the menu: P3.5.1.26
Use this parameter to select the digital input signal that activates a Quick Stop function. The Quick Stop function stops the drive
regardless of the control place or the state of the control signals.
11.7.4.27 (ID 447) Timer 1
Location in the menu: P3.5.1.27
AB298035655957en-000201 / DPD01083202 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON 100 FLOW Series and is the answer not in the manual?

Danfoss VACON 100 FLOW Series Specifications

General IconGeneral
BrandDanfoss
ModelVACON 100 FLOW Series
CategoryDC Drives
LanguageEnglish

Related product manuals