Use this parameter to select the digital input signal that activates the Fire Mode function. This parameter activates the Fire Mode if it
is enabled with a correct password.
11.7.4.38 (ID 1618) Fire Mode Reverse
Location in the menu: P3.5.1.40
Use this parameter to select the digital input signal that gives a command for reverse rotation direction during the Fire Mode. This
function has no effect in normal operation.
11.7.4.39 (ID 1715) Auto-Cleaning Activation
Location in the menu: P3.5.1.41
Use this parameter to select the digital input signal that starts the Auto-cleaning. The Auto-cleaning stops if the activation signal is
removed before the process is complete.
N O T I C E
If the input is activated, the drive starts.
11.7.4.40 (ID 426) Pump 1 Interlock
Location in the menu: P3.5.1.42
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.41 (ID 427) Pump 2 Interlock
Location in the menu: P3.5.1.43
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.42 (ID 428) Pump 3 Interlock
Location in the menu: P3.5.1.44
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.43 (ID 429) Pump 4 Interlock
Location in the menu: P3.5.1.45
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.44 (ID 430) Pump 5 Interlock
Location in the menu: P3.5.1.46
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.45 (ID 486) Pump 6 Interlock
Location in the menu: P3.5.1.47
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.46 (ID 487) Pump 7 Interlock
Location in the menu: P3.5.1.48
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.47 (ID 488) Pump 8 Interlock
Location in the menu: P3.5.1.49
AB298035655957en-000201 / DPD01083204 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON 100 FLOW Series and is the answer not in the manual?

Danfoss VACON 100 FLOW Series Specifications

General IconGeneral
BrandDanfoss
ModelVACON 100 FLOW Series
CategoryDC Drives
LanguageEnglish

Related product manuals