Use this parameter to select the digital input signal that activates the Fire Mode function. This parameter activates the Fire Mode if it
is enabled with a correct password.
11.7.4.38 (ID 1618) Fire Mode Reverse
Location in the menu: P3.5.1.40
Use this parameter to select the digital input signal that gives a command for reverse rotation direction during the Fire Mode. This
function has no effect in normal operation.
11.7.4.39 (ID 1715) Auto-Cleaning Activation
Location in the menu: P3.5.1.41
Use this parameter to select the digital input signal that starts the Auto-cleaning. The Auto-cleaning stops if the activation signal is
removed before the process is complete.
N O T I C E
If the input is activated, the drive starts.
11.7.4.40 (ID 426) Pump 1 Interlock
Location in the menu: P3.5.1.42
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.41 (ID 427) Pump 2 Interlock
Location in the menu: P3.5.1.43
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.42 (ID 428) Pump 3 Interlock
Location in the menu: P3.5.1.44
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.43 (ID 429) Pump 4 Interlock
Location in the menu: P3.5.1.45
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.44 (ID 430) Pump 5 Interlock
Location in the menu: P3.5.1.46
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.45 (ID 486) Pump 6 Interlock
Location in the menu: P3.5.1.47
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.46 (ID 487) Pump 7 Interlock
Location in the menu: P3.5.1.48
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-pump system. The selection of the
application with parameter P1.2 Application gives the default value.
11.7.4.47 (ID 488) Pump 8 Interlock
Location in the menu: P3.5.1.49
AB298035655957en-000201 / DPD01083204 | Danfoss A/S © 2023.08
Parameter Descriptions