Selection
number
Selection name
Description
0
Not used
The output is not used.
1
Ready
The AC drive is ready to operate.
2
Run
The AC drive operates (the motor runs).
3
General fault
A fault trip occurred.
4
General fault inverted
A fault trip did not occur.
5
General alarm
An alarm occurred.
6
Reversed
The reverse command is given.
7
At speed
The output frequency has become the same as the set frequency reference.
8
Thermistor fault
A thermistor fault occurred.
9
Motor regulator activated
One of the limit regulators (for example current limit or torque limit) is activated.
10
Start signal active
The start command of the drive is active.
11
Keypad control active
The selection is keypad control (the active control place is keypad).
12
I/O control B active
The selection is I/O control place B (the active control place is I/O B).
13
Limit supervision 1
The limit supervision activates if the signal value goes below or above the set su-
pervision limit (P3.8.3 or P3.8.7).
14
Limit supervision 2
The limit supervision activates if the signal value goes below or above the set su-
pervision limit (P3.8.3 or P3.8.7).
15
Fire mode active
The Fire mode function is active.
16
Flushing active
The Flushing function is active.
17
Preset Frequency active
The selection of preset frequency was made with digital input signals.
18
Quick Stop active
The Quick stop function is activated.
19
PID in Sleep mode
The PID controller is in the sleep mode.
20
PID Soft Fill activated
The Soft fill function of the PID controller is activated.
21
PID feedback supervision
The feedback value of the PID controller is not in the supervision limits.
22
ExtPID feedback supervision
The External PID controller feedback value is not in the supervision limits.
23
Input pressure alarm
The input pressure of the pump is below the value that was set with parameter
P3.13.9.7.
24
Frost protection alarm
The measured temperature of the pump is below the level that was set with pa-
rameter P3.13.10.5.
25
Time channel 1
The status of Time channel 1.
26
Time channel 2
The status of Time channel 2.
27
Time channel 3
The status of Time channel 3.
28
Fieldbus Control Word bit 13
The digital (relay) output control from the Fieldbus control word bit 13.
29
Fieldbus Control Word bit 14
The digital (relay) output control from the Fieldbus control word bit 14.