55
Multi-pump K7 control
The contactor control for the Multi-pump function.
56
Multi-pump K8 control
The contactor control for the Multi-pump function.
69
Selected parameter set
Shows the active parameter set:
OPEN = Parameter set 1 active
CLOSED = Parameter set 2 active
72
AHF Capacitor Disconnection
73
AHF Capacitor Disconnection
Inverted
74
Run Indication
75
Motor Switch Open
The Motor Switch function has detected that the switch between the drive and
the motor is open.
11.7.6.2 (ID 11002) RO1 ON Delay
Location in the menu: P3.5.3.2.2
Use this parameter to set the ON delay for the relay output.
11.7.6.3 (ID 11003) RO1 OFF Delay
Location in the menu: P3.5.3.2.3
Use this parameter to set the OFF delay for the relay output.
11.7.7 Analog Outputs
11.7.7.1 (ID 10050) AO1 Function
Location in the menu: P3.5.4.1.1
Use this parameter to select a function or a signal that is connected to the analog output. The contents of the analog output signal 1
are specified in this parameter. The scaling of the analog output signal depends on the signal.
Selection
number
Selection name
Description
0
Test 0% (Not used)
The analog output is set to 0% or 20% so that it agrees with parameter P3.5.4.1.3.
1
TEST 100%
The analog output is set to 100% of the signal (10 V/20 mA).
2
Output frequency
The actual output frequency from 0 to Maximum frequency reference.
3
Frequency reference
The actual frequency reference from 0 to Maximum frequency reference.
4
Motor speed
The actual motor speed from 0 to Motor nominal speed.
5
Output current
The output current of the drive from 0 to Motor nominal current.
6
Motor torque
The actual motor torque from 0 to motor nominal torque (100%).
7
Motor power
The actual motor power from 0 to Motor nominal power (100%).
8
Motor voltage
The actual motor voltage from 0 to Motor nominal voltage.
9
DC link voltage
The actual DC link voltage 0…1000 V.
10
PID Setpoint
The actual setpoint value of the PID Controller (0…100%).
AB298035655957en-000201 / DPD01083212 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide