N O T I C E
WARRANTY BECOMING VOID
The warranty is void if the Fire mode function is activated.
Use Test mode to test the Fire mode function and the warranty stays valid.
11.19.2 (ID 1599) Fire Mode Password
Location in the menu: P3.17.1
Use this parameter to enable the fire mode function.
N O T I C E
All other fire mode parameters are locked when the fire mode is enabled and correct password is set in this parameter.
Selection num-
ber
Selection name
Description
1002
Enabled mode
The drive resets all the faults and continues to operate at the same speed until it is not
possible.
1234
Test mode
The drive does not automatically reset the faults, and the drive stops when a fault occurs.
11.19.3 (ID 1617) Fire Mode Frequency Source
Location in the menu: P3.17.2
Use this parameter to select the frequency reference source when the fire mode is active. This parameter enables the selection of,
for example, the AI1, or the PID controller as the reference source when operating the fire mode.
11.19.4 (ID 1598) Fire Mode Frequency
Location in the menu: P3.17.3
Use this parameter to set the frequency that is used when Fire mode is active. The drive uses this frequency when the value of
parameter P3.17.2 Fire Mode Frequency Source is Fire Mode Frequency.
11.19.5 (ID 1596) Fire Mode Activation on Open
Location in the menu: P3.17.4
Use this parameter to select the digital input signal that activates the Fire Mode function. If this digital input signal is activated, an
alarm shows on the display, and the warranty becomes void. The type of this digital input signal is NC (normally closed).
It is possible to try the Fire mode with the password that activates the Test mode. Then the warranty stays valid.
N O T I C E
If Fire mode is enabled, and the correct password is given to the parameter Fire Mode Password, all the Fire mode parameters
become locked. To change the Fire mode parameters, change the value of P3.17.1 Fire Mode Password to 0 first.
AB298035655957en-000201 / DPD01083 | 271Danfoss A/S © 2023.08