Cleaning
Forward Frequency
Cleaning
Reverse Frequency
Cleaning Cycles
e30bg326.10
Illustration 103: The Auto-cleaning Function
11.22.2 Jockey Pump
11.22.2.1 (ID 1674) Jockey Function
Location in the menu: P3.21.2.1
Use this parameter to control the Jockey pump function. A Jockey pump is a smaller pump that keeps the pressure in the pipeline,
when the main pump is in the sleep mode. It can occur, for example, in the night.
The Jockey pump function controls a jockey pump with a digital output signal. A jockey pump can be used if a PID controller is used
to control the main pump. The function has 3 operation modes.
The jockey pump starts when the PID Sleep of the main pump activates. The jockey pump stops
when the main pump wakes up from the sleep mode.
The jockey pump starts when the PID Sleep activates, and the PID feedback signal is less than
the level set by parameter P3.21.2.2.
The jockey pump stops when the PID feedback signal is more than the level set in parameter
P3.21.2.3 or the main pump wakes up from the sleep mode.
AB298035655957en-000201 / DPD01083276 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide