The baseline run goes through 10 frequency points including 10 steady and 9 ramp states. It collects the minimum, maximum,
mean, and standard deviation values, and stores the statistical baseline data in arrays. Normal start command is required after base-
line run start.
Time
f
Base0
f
Base1
f
BaseN
...
Baseline Run Duration
Baseline Start
Normal ramps
Slow ramps
(Baseline MinFreq)
Frequency
(Baseline MaxFreq)
e30bi555.10
Illustration 108: BaselineRun Start
11.24.3 (ID 3502) BaselineRun MinFreq
Location in the menu: P3.24.2.2
Use this parameter to set frequency point where baseline run is started.
11.24.4 (ID 3503) BaselineRun MaxFreq
Location in the menu: P3.24.2.3
Use this parameter to set frequency point where baseline run is ended.
11.24.5 (ID 3504) BaselineRun Duration
Location in the menu: P3.24.2.4
Use this parameter to set the duration of the baseline run.
11.24.6 Manual Run
Before or after baseline run, each measurement point can be modified by parameter. One array includes 10 points in steady state
and 9 points in ramp state.
11.24.6.1 (ID 3506) Modified Array
Location in the menu: P3.24.2.5
Use this parameter to select a modified array.
11.24.6.2 (ID 3507) Modified Point
Location in the menu: P3.24.2.6
Use this parameter to select which measurement point to modify in the array. Steady array includes 10 points and ramp array in-
cludes 9 points. First point has value 0.
11.24.6.3 (ID 3508) Modified Value
Location in the menu: P3.24.2.7
Use this parameter to give new value to the point selected with ID 3507.
11.24.6.4 (ID 3505) Modified Activation
Location in the menu: P3.24.2.8
Before or after the baseline run, each measurement point can be modified. Use this parameter to activate the Modified value (ID
3508) of the Modified point (ID 3507).
11.24.6.5 (ID 3509) Baseline Data Selector
Location in the menu: P3.24.2.9
Use this parameter to select which array points can be monitored in monitor group M2.16.1 Baseline data.