Table 133: Default Values of Parameters of Group 3.3
Index
Parameter
Standard
applica-
tion
HVAC
applica-
tion
PID
control
applica-
tion
Multi-
pump
(single
drive) ap-
plication
Multi-
pump
(multi-
drive) ap-
plication
Unit
ID
Description
3.3.1.5
I/O A Ref Sel
6
6
7
7
7
117
6 = AI1 + AI2
7 = PID
3.3.1.6
I/O B Ref Sel
4
4
4
4
4
131
4 = AI1
3.3.1.7
Keypad Ref Sel
2
2
2
2
2
121
2 = Keypad Refer-
ence
3.3.1.10
Fieldbus Ref Sel
3
3
3
3
3
122
3 = Fieldbus Ref-
erence
3.3.3.1
Preset Freq Mode
0
0
0
0
0
182
0 = Binary Coded
3.3.3.3
Preset Freq 1
10.0
10.0
10.0
10.0
10.0
Hz
105
3.3.3.4
Preset Freq 2
15.0
15.0
15.0
15.0
15.0
Hz
106
3.3.3.5
Preset Freq 3
20.0
20.0
20.0
20.0
20.0
Hz
126
P3.3.6.1
Flushing Refer-
ence Activation
0
0
0
0
101
530
0 = DigIN Slot0.1
101 = DigIN Slo-
tA.2
P3.3.6.2
Flushing Refer-
ence
0
0
0
0
0
Hz
1239
Table 134: Default Values of Parameters of Group 3.5
Index
Parameter
Stand-
ard ap-
plication
HVAC
applica-
tion
PID
control
appli-
cation
Multi-
pump
(single
drive)
applica-
tion
Multi-
pump
(multi-
drive)
applica-
tion
Unit
ID
Description
3.5.1.1
Ctrl Signal 1 A
100
100
100
100
100
403
100 = DigIN SlotA.1
3.5.1.2
Ctrl Signal 2 A
101
101
0
0
0
404
0 = DigIN Slot0.1
101 = DigIN SlotA.2
3.5.1.4
Ctrl Signal 1 B
0
0
103
101
0
423
0 = DigIN Slot0.1
101 = DigIN SlotA.2
103 = DigIN SlotA.4
3.5.1.7
I/O B Ctrl Force
0
0
105
102
0
425
0 = DigIN Slot0.1
102 = DigIN SlotA.3
105 = DigIN SlotA.6
3.5.1.8
I/O B Ref Force
0
0
105
102
0
343
0 = DigIN Slot0.1
102 = DigIN SlotA.3
105 = DigIN SlotA.6
AB298035655957en-000201 / DPD01083290 | Danfoss A/S © 2023.08