Parameter
Standard
applica-
tion
HVAC
applica-
tion
PID
control
applica-
tion
Multi-
pump
(single
drive) ap-
plication
Multi-
pump
(multi-
drive) ap-
plication
Unit
ID
Description
102 = DigIN SlotA.3
3.13.2.6
PID Setpoint
Source 1
-
-
1
1
1
332
1 = Keypad Setpoint
1
P3.13.2.10
PID Setpoint
Source 2
-
-
-
-
2
431
2 = Keypad Setpoint
2
3.13.3.1
PID Feedback
Function
-
-
1
1
1
333
1 = Only Source 1 in
use
3.13.3.3
PID Feedback
Source
-
-
2
2
2
334
2 = AI2
Table 137: Default Values of Parameters of Group 3.15
Index
Parameter
Standard
applica-
tion
HVAC
applica-
tion
PID
control
appli-
cation
Multi-
pump
(single
drive) ap-
plication
Multi-
pump
(multi-
drive) ap-
plication
Unit
ID
Description
P3.15.1
Multi-pump Mode
-
-
-
0
2
1785
0= Single drive
1= Multifollower
2= Multimaster
P3.15.2
Number of Pumps
1
1
1
3
3
1001
P3.15.5
Pump Interlocking
-
-
-
1
1
1032
0 = Disabled
1 = Enabled
P3.15.6
Autochange
-
-
-
1
1
1027
0 = Disabled
1 = Enabled (inter-
val)
2 = Enabled
(weekdays)
P3.15.7
Autochanged
Pumps
-
-
-
1
1
1028
0 = Auxiliary Pump
1 = All Pumps
P3.15.8
Autochange Inter-
val
-
-
-
48.0
48.0
h
1029
P3.15.11
Autochange Fre-
quency Limit
-
-
-
25.0
25.0
Hz
1031
P3.15.12
Autochange Pump
Limit
-
-
-
1
3
1030
P3.15.13
Bandwidth
-
-
-
10.0
10.0
%
1097
AB298035655957en-000201 / DPD01083 | 293Danfoss A/S © 2023.08