Troubleshooting
Check the control panel connection and the control panel cable if you have it.
12.3.103 Fault Code 53, ID 1053 - Fieldbus Communication Fault
Cause
The data connection between the fieldbus master and the fieldbus board is defective.
Troubleshooting
Check the installation and fieldbus master.
12.3.104 Fault Code 53, ID 1054 - Redundant Switchover
Cause
The data connection between controlling fieldbus and the drive has timed out. Redundant control has changed the controlling
fieldbus connection.
Troubleshooting
Check the installation and the communication cables.
12.3.105 Fault Code 53, ID 1055 - Redundant Timeout
Cause
The data connection between controlling fieldbus protocols and the drive has timed out.
Troubleshooting
Check the installation and the communication cables.
12.3.106 Fault Code 54, ID 1354 - Slot A fault
Cause
A defective option board or slot.
Troubleshooting
Check the board and the slot.
Ask for instructions from your nearest distributor.
12.3.107 Fault Code 54, ID 1454 - Slot B fault
Cause
A defective option board or slot.
Troubleshooting
Check the board and the slot.
Ask for instructions from your nearest distributor.
12.3.108 Fault Code 54, ID 1554 - Slot C fault
Cause
A defective option board or slot.
Troubleshooting
Check the board and the slot.
Ask for instructions from your nearest distributor.
12.3.109 Fault Code 54, ID 1654 - Slot D fault
Cause
A defective option board or slot.
Troubleshooting
Check the board and the slot.
Ask for instructions from your nearest distributor.