An individual switch that has an auto, off and man setting controls each drive. Terminal 17 connects +24V between the drive 1 and
2. External diodes are connected between terminals 1 and 2. The digital input signals use negative logic (ON = OV).
P1.2 Application = Multipump(MultiDrive)
P3.15.3 Pump ID Number = 1
P3.15.4 Start & Feedback = Signals Connected
Reference voltage
NOT USED (0...10V)
OUTPUT FREQUENCY
(0...20mA)
PID FEEDBACK (4...20mA)
24V auxilary voltage out
24V auxilary voltage in
I/O ground
I/O ground
FAULT RESET
EXTERNAL FAULT
START FORWARD
Common for DI1-DI6
Common for DI1-DI6
24V auxilary voltage out
PUMP INTERLOCK
(Not in use by default)
Drive-To-Drive
Communication
(Modbus RTU)
Relay Output 1 (RUN)
Relay Output 2
(FAULT)
Relay Output 3
(READY)
FLUSHING
(Start Forward + Flushing Freq.)
PID SETPOINT SELECT.
(Open=Keypad SP1, Closed=Keypad SP2)
RO1
RO1
RO1
RO2
RO2
RO2
RO3
RO3
+10V
Illustration 29: Electric Wiring Diagram of the Multi-pump (Multidrive) System, Example 4A