P3.5.1.44
Pump 3 Interlock
DigIN Slot0.1
()
428
OPEN = Not active
CLOSED = Active
P3.5.1.45
Pump 4 Interlock
DigIN Slot0.1
429
OPEN = Not active
CLOSED = Active
P3.5.1.46
Pump 5 Interlock
DigIN Slot0.1
430
OPEN = Not active
CLOSED = Active
P3.5.1.47
Pump 6 Interlock
DigIN Slot0.1
486
OPEN = Not active
CLOSED = Active
P3.5.1.48
Pump 7 Interlock
DigIN Slot0.1
487
OPEN = Not active
CLOSED = Active
P3.5.1.49
Pump 8 Interlock
DigIN Slot0.1
488
OPEN = Not active
CLOSED = Active
P3.5.1.52
Reset kWh Trip Counter
DigIN Slot0.1
1053
P3.5.1.53
Parameter Set 1/2 Selection
DigIN Slot0.1
496
OPEN = Parameter Set 1
CLOSED = Parameter Set 2
P3.5.1.54
Multi-Setpoint Selection 0
DigIN Slot0.1
15576
P3.5.1.55
Multi-Setpoint Selection 1
DigIN Slot0.1
15577
P3.5.1.56
Multi-Setpoint Selection 2
DigIN Slot0.1
15578
P3.5.1.57
Multi-Setpoint Selection 3
DigIN Slot0.1
15579
P3.5.1.58
Flow Switch
DigIN Slot0.2
15590
P3.5.1.59
AHF Over Temperature
DigIN Slot0.2
15513
1
The selection of the application with parameter P1.2 Application gives the default value. See the default values in
11.25 Default Values of Parame-
ters in the Different Applications.
N O T I C E
Your option board and board setup give the number of available analogue inputs. The standard I/O board has 2 analog inputs.
Table 45: Analog Input 1 Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.1.1
AI1 Signal Selection
AnIN SlotA.1
(1)
377
P3.5.2.1.2
AI1 Signal Filter Time
0.00
300.00
s
0.1
(1)
378
P3.5.2.1.3
AI1 Signal Range
0
1
0
(1)
379
0 = 0…10 V/0…20 mA
1 = 2…10 V/4…20 mA
AB298035655957en-000201 / DPD01083 | 97Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide